42U and 26U describe rack units, not usable battery space
A 19-inch rack unit is 44.45mm high. A 42U cabinet provides 1,867mm of nominal rack height, and a 26U cabinet provides 1,156mm. Those figures describe the mounting aperture, not the outside height of the enclosure. A 3U battery module is 133mm high, so the U count converts to a battery count by division.
The cabinet also needs frame, plinth, door, cable entry and airflow space. That is why a 42U cabinet does not hold 42U of batteries, and a 26U cabinet does not hold 26U. The working number is the rack space left after the rectifier, distribution and cable management are placed.
A 42U cabinet holds 14 x 48V 100Ah modules before services
The indoor telecom cabinet line runs from 10U to 47U. The indoor cabinet datasheet lists “Capacity: 10U / 12U / 15U / 18U / 22U / 27U / 32U / 37U / 42U / 47U”. It uses a 19-inch rack, SPCC cold-rolled steel, a tempered-glass door and IP20 protection.
A 48V 100Ah module is 3U high. Forty-two divided by three is 14, so 14 modules fit with the rack completely filled. That is 67.2kWh nominal, 14 x 4.8kWh, and 602kg of batteries before the cabinet, rectifier and cabling. No site should plan a bank with zero service space.
| Cabinet | Rack units | Module height | Modules with no services | Nominal energy | Battery weight | Protection |
|---|---|---|---|---|---|---|
| Indoor cabinet | 42U | 3U | 14 | 67.2kWh | 602kg | IP20 |
| Outdoor cabinet | 26U | 3U | 8 | 38.4kWh | 344kg | IP65 |
The table assumes the 48V 100Ah module in every slot. A 48V 50Ah module also uses 3U but stores 2.4kWh, so it halves the energy for the same rack space. A 48V 150Ah or 200Ah module uses 4U, which changes the arithmetic.
A 26U cabinet holds 8 x 48V 100Ah modules before services
The outdoor telecom cabinet line runs from 6U to 26U and is rated IP65. The 26U model has a 19-inch four-post rack, 45mm EPS insulation and a 600 x 450mm or 600 x 600mm footprint. It is built for base stations, roadside cabinets and other outdoor sites.
Twenty-six divided by three is 8.67, so eight modules fit and 2U remain. That is 38.4kWh nominal and 344kg of batteries. Nine modules need 27U, one more than the cabinet provides.
Reserve 5U to 8U for rectifiers, breakers and cable entry
A working layout needs space above the batteries. A rectifier shelf, DC distribution, breakers, cable entry and blanking panels for airflow usually take 3U to 6U. The table below uses 2U, 5U and 8U reservations so the battery count can be compared directly.
| Cabinet | Space reserved | Modules | Rack used | Spare | Nominal energy | Battery weight |
|---|---|---|---|---|---|---|
| 42U | 4U | 12 | 36U | 2U | 57.6kWh | 516kg |
| 42U | 6U | 12 | 36U | 0U | 57.6kWh | 516kg |
| 42U | 8U | 11 | 33U | 1U | 52.8kWh | 473kg |
| 26U | 2U | 8 | 24U | 0U | 38.4kWh | 344kg |
| 26U | 5U | 7 | 21U | 0U | 33.6kWh | 301kg |
| 26U | 8U | 6 | 18U | 0U | 28.8kWh | 258kg |
The common comparison is 12 modules in the 42U cabinet with 6U reserved against seven modules in the 26U cabinet with 5U reserved. That is 57.6kWh against 33.6kWh, a difference of 24kWh, and 516kg against 301kg, a difference of 215kg. The 42U layout stores 71% more energy and carries 71% more battery weight. The cabinet structure and the floor have to accept both.
Depth rules out some modules before the U count does
The 48V 100Ah module measures 442 x 420 x 133mm and reaches 482mm deep with handles and terminals. The indoor cabinet has a 600 x 800mm or 800 x 800mm footprint, so an 800mm external depth leaves room for the module, door hardware and cable bend. The outdoor cabinet has a 600 x 600mm footprint, and the 45mm EPS lining takes about 90mm from the internal depth. That leaves roughly 510mm before door hardware, against a 482mm module. The fit is tight, so confirm the usable internal depth with the factory before ordering.
The 48V 200Ah module is 610mm deep and will not fit a 600mm outdoor cabinet. It suits the indoor cabinet with the 800mm footprint. The 48V 150Ah module is 440mm deep and the 48V 50Ah module is 325mm deep, so both leave more depth margin.
Weight and floor loading scale with the module count
A 48V 100Ah module weighs 43kg. Twelve modules weigh 516kg, fourteen weigh 602kg and seven weigh 301kg. Add the cabinet, rectifier, breakers and cabling. The floor, raised floor or outdoor pad has to carry that load, and the cabinet shelf or bracket has to support each module.
Mount the heaviest modules in the lowest positions. A 43kg module is a two-person lift, and a full 42U bank needs a planned access route, not a ladder and one technician. The indoor cabinet datasheet does not publish a universal shelf load rating, so the project should confirm the rating for the exact module and bracket arrangement.
IP20 indoor and IP65 outdoor cabinets serve different sites
The 42U cabinet is an indoor model with IP20 protection. It belongs in a telecom room, shelter or data center with controlled temperature, humidity and dust. The 26U cabinet is an outdoor model with IP65 protection against dust and water jets, 45mm EPS insulation and fan cooling. It belongs on a pad, a pole or a roadside site.
The choice often follows the site before the load. If the site has an equipment room, the 42U indoor cabinet gives the larger bank and easier service access. If the site is outdoor, the published outdoor line stops at 26U, so a larger bank needs two cabinets or a shelter. Do not put an IP20 cabinet outdoors and call it weatherproof.
Rectifier settings and commissioning checks
All four 48V rack models use the same charge profile: 53.3V equalization, 51.0V float and 40.5V cutoff. Set the rectifier before the batteries are connected. A rectifier left on a lead-acid profile will not charge the LiFePO4 bank correctly, and a voltage above the BMS cutoff will trip the modules.
Twelve modules at 100A each add up to 1,200A of potential bank current. The busbar, main breaker and cable have to be sized for the bank current, not the module current. Every string also needs its own breaker or fuse. Check the ventilation path, the door clearance and the lifting route before the cabinet is fixed to the floor.
The indoor telecom cabinet product page lists the 10U to 47U sizes, and the outdoor telecom cabinet page lists the 6U to 26U IP65 range. The telecom battery cabinet supplier page covers enclosure selection, and the 26U battery count guide works through the smaller cabinet in detail. The 48V 100Ah rack battery is the module used in the tables.
Frequently asked questions
Fourteen modules fit if the whole rack is given to batteries, because each module is 3U and 42 divided by 3 is 14. A working layout with 6U reserved for a rectifier and distribution holds 12 modules, or 57.6kWh nominal.
Eight modules fit with no service space, because 26 divided by 3 is 8.67. A working layout with 5U reserved holds seven modules, or 33.6kWh nominal.
The 42U model is an indoor cabinet with IP20 protection. The outdoor cabinet line stops at 26U and carries IP65 protection. An outdoor site that needs more than 26U of batteries needs two cabinets or a shelter, not an indoor cabinet placed on a pad.
The module is 482mm deep with handles and terminals. An indoor cabinet with an 800mm external depth leaves usable clearance. A 600 x 600mm outdoor cabinet leaves roughly 510mm after the 45mm EPS lining, so confirm the internal depth before ordering.
Twelve 48V 100Ah modules weigh 516kg. Fourteen modules weigh 602kg. Add the cabinet, rectifier, breakers and cabling, then confirm the floor or pad load rating and the cabinet shelf rating for the exact layout.
Sources: LINEX Indoor Telecom Cabinet datasheet (10U to 47U, 19-inch rack, 600 x 800mm or 800 x 800mm, SPCC, IP20, checked 2026-11-16); LINEX IP65 Outdoor Telecom Cabinet datasheet (6U to 26U, 600 x 450mm or 600 x 600mm, 45mm EPS, IP65, checked 2026-11-16); LINEX 48V 50Ah datasheet (2,400Wh, 3U, 29kg, 483 x 325 x 133mm, checked 2026-11-16); LINEX 48V 100Ah datasheet (4,800Wh, 3U, 43kg, 442 x 420 x 133mm, 482mm with handles, 100A, 53.3V equalization, 51.0V float, 40.5V cutoff, checked 2026-11-16); LINEX 48V 150Ah datasheet (7,200Wh, 4U, 60kg, 482 x 440 x 178mm, checked 2026-11-16); LINEX 48V 200Ah datasheet (9,600Wh, 4U, 78kg, 482 x 610 x 178mm, checked 2026-11-16); Wikipedia, 19-inch rack (1U = 44.45mm, checked 2026-11-16); LINEX 26U battery count guide (26U arithmetic and 600 x 600mm depth check, checked 2026-11-16). Last updated 2026-11-16.